Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL COMMENT:
1. Because of the complete change of all the documents from the original approved set, deletion of two sheets and adding of 11 new sheets, this project is requierd to have a complete new code review.

SHEET ASP-1
1. The Site Plan must be submitted to the CDRC for approval. A copy of the approved site plan must be submitted with the drawings.
SHEET S1.3
2. Please provide Special Inspectors Certificates for all the special inspections required as outlined on this sheet.
STRUCTURAL DRAWINGS
3. The structural drawings for this project can not be reviewed with out a complete set of structural calculations. Please submit same.
SHEET A1:
4. There are inconsistances with the section detail references: reference 7/A5.2 should be 8/A5.2. Please check all detail references and insure proper section is referenced.
SHEET SP1
5. Lettering font sizes are noncompliant. Change all lettering to 3/32" minimum height upper and lower case.

END OF REVIEW
12/16/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/16/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide roof drainage calculations (i.e. the roof areas served by each roof drain or scupper). All roof areas shall be drained by roof drains, scuppers, or gutters. Reference: Section 1101.11.1, UPC 2006.
2. Provide calculations to show that the size of the overflow in the roof drain collector box has a drainage capacity equal to that of the scupper. Reference: Section 1101.11.2.2.1, UPC 2006.
3. Revise the overflow drain (detail 5/A7) strainer to comply with the requirements of Section 1105.2, UPC 2006.
12/22/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2009 CPIERCE1 OUT TO CUSTOMER Completed