Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T07CM03337
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/14/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/18/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |