Permit Number: T07CM03336
Parcel: 12704293A

Address:
4901 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03336
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
08/10/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a sealed mechanical drawing.
2. Show how the ventilation for the waiting oom will be changed due to the expansion of the room.
3. Provide a design for the support for the A/C unit.
4. Show how the condensate from the A/C unit will be disposed.
08/10/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/10/2007 ROBERT SHERRY WATER REVIEW Approved
08/10/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please provide additional information regarding the rated wall assemblies and relocated doors at the south stairwell in order to verify compliance with chapter 7 of the 2006 IBC.

2) Please provide the total valuation and the value of the work done to increase accessibility on the plans in order to verify compliance with section 3409.7 of the 2006 IBC.

3) Please revise the tenant space occupancy group per chapter 3 of the 2006 IBC (B vs. M).

4) Please seal all sheets in accordance with the submittal requirements of the City of Tucson.
08/10/2007 RSHERRY1 WWM REVIEW Passed
08/10/2007 MARTIN BROWN FIRE REVIEW Approved
08/10/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/05/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03336 8/10/07

1. Please have Mechanical Engineer clarify power requirements for the new AC unit. The specifications call for a minimum disconnect size, which is not typically specified. Please provide power consumption requirements, MOCP, and MCA as applicable.
2. Mechanical has specified a 240V AC. Electrical has provided 208V power. Coordinate with Mechanical and clarify.
3. Mechanical shall sign and date seal to incorporate AC into scope of work.
09/05/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review