Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03329
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Section 707.4, exception (4), states that "An approved type of two-way fitting (singular)…may be used as a substitute for an upper terminal cleanout." The use of an assembly of fitting as shown in your detail is not allowed by Section 707.6, UPC 2006. Provide either a listed two-way cleanout fitting or install a one-way cleanout. Reference Sections 103.2.3 and 707.6, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/25/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 09/25/2007 | CINDY AGUILAR | REJECT SHELF | Completed |