Permit Number: T07CM03329
Parcel: Unknown

Address:
10 S HOUGHTON RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03329
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section 707.4, exception (4), states that "An approved type of two-way fitting (singular)…may be used as a substitute for an upper terminal cleanout." The use of an assembly of fitting as shown in your detail is not allowed by Section 707.6, UPC 2006. Provide either a listed two-way cleanout fitting or install a one-way cleanout. Reference Sections 103.2.3 and 707.6, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
09/25/2007 CINDY AGUILAR REJECT SHELF Completed