Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03329
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/09/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/20/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/27/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/04/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/04/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Provide the listing for the two-way cleanout fitting called out in the front of store plumbing plan. Reference Sections 103.2.3 and 707.6, UPC 2006. |
09/04/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/05/2007 | GERRY KOZIOL | WWM | REVIEW | Approv-Cond | 1: BASHAS- MONTESSA CENTER-FRONT STORE 2: UNDERGROUND PLUMBING FOR FUTURE TI (RESTAURANT)-ISSUED W/1050 GAL GREASE INTERCEPTOR 3: NO TI'S UNTIL SEWER CONNECTION FEES ARE PAID 4: NO WASTEWATER PLUMBING STUB-OUTS. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/14/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
09/14/2007 | GERARDO BONILLA | REJECT SHELF | Completed |