Permit Number: T07CM03326
Parcel: 11309300A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM03326
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity: T07CM03326
Date: 9/19/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

I. GENERAL REQUIREMENTS:
· Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

II. SITE PLAN:
· Overhead service for new construction requires an appeal to the Building Official, UAC amendment section 108.

III. ELEVATIONS:
· Provide an attic space ventilation calculation and note the size and location of all attic vents needed to comply, R806.2.

IV. PLUMBING PLAN:
§ Cleanouts are required at the kitchen sink area UPC 707.4 W/ State amendment.

V. ELECTRICAL PLAN:
· Specify overcurrent protection for range on panel schedule.
· Site plan specifies overhead electric service and riser diagram on electrical page specifies underground service, please clarify.
· Clarify range circuit reference on plan view.
· Bedroom outlets shall be arc-fault protected (receptacles, lights, and smoke detectors), E3802.12.

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
09/25/2007 CINDY AGUILAR REJECT SHELF Completed