Permit Number: T07CM03321
Parcel: 126080290

Address:
4106 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03321
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2007 MARTIN BROWN FIRE REVIEW Denied IFC 903.2.7 Group R Need to add a fire sprinkler system for Occ loads over 5. Please add on plans fire sprinkler system will be installed.

Need fire hydrant(s) location showing on site plans.
11/23/2007 PAUL MACHADO ENGINEERING REVIEW Approved
11/23/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03321 11/23/07

1. Provide the required receptacle in the south bathroom. Reference NEC 210.52 (D).
2. Ckt 3 has a required bathroom receptacle and other loads. Not permitted by NEC 210.11 (C) (3).
3. Please provide power requirements for the AC.
4. Remove all references to the IRC and use NEC.
5. Provide a maintenance receptacle, per NEC 210.63, for the AC.
6. Provide AFCI, per NEC 210.12, for all bedroom circuits.
7. Demonstrate compliance with the Tucson Lighting Code.
8. Add the Heater, Furnace, Smoke Detectors, Disposal, and Refrigerator to the load calculations.
9. Demonstrate that no phase is overloaded.
11/23/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved 1. SHOW H/C COMPLIANCE OF BOTH TOILETS ON DRAWINGS
2. PROVIDE ADDITIONAL INFORMATION OF EXISTING SHELL COMPLETED UNDER A SEPARATE ACTIVITY NUMBER
11/23/2007 STEVE SHIELDS ZONING REVIEW Approved
12/14/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/14/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct the sizes of the new gas piping and the gas demand .
2. Provide water and waste & vent diagrams.
3. Clarify the plumbing notes to apply to this activity.
4. Indicate the material used for the existing water service pipe that goes under the new addition.
5. Show how the water heater flue penetrates the roof, the size of the flue and its height.
12/14/2007 ROBERT SHERRY WATER REVIEW Denied Provide a reduced pressure backflow preventer at the water meter service.
12/14/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/14/2007 GBONILL1 WWM REVIEW Needs Review