Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03321
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2007 | MARTIN BROWN | FIRE | REVIEW | Denied | IFC 903.2.7 Group R Need to add a fire sprinkler system for Occ loads over 5. Please add on plans fire sprinkler system will be installed. Need fire hydrant(s) location showing on site plans. |
| 11/23/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 11/23/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03321 11/23/07 1. Provide the required receptacle in the south bathroom. Reference NEC 210.52 (D). 2. Ckt 3 has a required bathroom receptacle and other loads. Not permitted by NEC 210.11 (C) (3). 3. Please provide power requirements for the AC. 4. Remove all references to the IRC and use NEC. 5. Provide a maintenance receptacle, per NEC 210.63, for the AC. 6. Provide AFCI, per NEC 210.12, for all bedroom circuits. 7. Demonstrate compliance with the Tucson Lighting Code. 8. Add the Heater, Furnace, Smoke Detectors, Disposal, and Refrigerator to the load calculations. 9. Demonstrate that no phase is overloaded. |
| 11/23/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | 1. SHOW H/C COMPLIANCE OF BOTH TOILETS ON DRAWINGS 2. PROVIDE ADDITIONAL INFORMATION OF EXISTING SHELL COMPLETED UNDER A SEPARATE ACTIVITY NUMBER |
| 11/23/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/14/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/14/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Correct the sizes of the new gas piping and the gas demand . 2. Provide water and waste & vent diagrams. 3. Clarify the plumbing notes to apply to this activity. 4. Indicate the material used for the existing water service pipe that goes under the new addition. 5. Show how the water heater flue penetrates the roof, the size of the flue and its height. |
| 12/14/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a reduced pressure backflow preventer at the water meter service. |
| 12/14/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/14/2007 | GBONILL1 | WWM | REVIEW | Needs Review |