Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM03302
Parcel: 12701004C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03302
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/21/2007 DAVE MANN FIRE REVIEW Denied Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.

Also, it is unclear how the fire sprinkler system is being supplied. Please clarify.
08/22/2007 ROBERT SHERRY WATER REVIEW Approved
08/27/2007 CAGUILA1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2007 CINDY AGUILAR APPROVAL SHELF Completed
08/27/2007 CINDY AGUILAR OUT TO CUSTOMER Completed