Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03300
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/08/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/08/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03300 8/8/07 1. Electrical load on Ckt 12 is 2166VA, or 2707VA considering continuous loading. This would put 23A on a 20A circuit. 2. Panel appears overloaded. Reference NEC 220.87. |
| 08/08/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/08/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/08/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/09/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 08/09/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 08/09/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 08/09/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |