Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03292
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the submitted energy code calculations for the building envelope to coordinate with the building construction shown on the drawings. Roof 1 is shown as having R-30 batt insulation in the truss cavities not R-39 batt insulation (Details 8 & 9, sheet a6). Roof 2 is not shown as having any continuous insulation on the drawings. Exterior wall 2 is noted as having wood furring and R-10 batt insulation but the calculations claim metal furring with R-19 cavity insulation. The calculations also claim that exterior wall 2 has R-8 continuous insulation but it is not clear how that is being provided. None of the glazing is noted as having any particular U-value or SHGC requirements on the drawing. Reference: Section 104.2, International Energy Conservation Code 2006 2. Comment not addressed. Revise the energy code analysis, using the correct climate zone for Pima County < 4,000 feet. The town of Pima, Arizona is located northwest of Safford, Arizona. Reference: Section 302.2, IECC 2006, as amended by the City of Tucson. |
| 02/28/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Sixth request. Provide justification for not connecting the building sewer to the public sewer. Reference: Section 305.0, UPC 2006. 2. Comment not addressed. Keynote 10 on sheet a3 refers to scuppers; are you meaning to say "gutters"? Details 8 and 9, sheet a6, show a scupper: where does this occur? Reference: Section 103.2.3, UPC 2006. |
| 03/01/2011 | SEPTIC APPROVAL | WWM | REVIEW | Denied | need septic permit w/Pima County NO SEPTIC RECORDS |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/17/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |