Permit Number: T07CM03292
Parcel: 11518054A

Address:
710 W CARMEN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03292
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Fifth request. Provide justification for not connecting the building sewer to the public sewer. Reference: Section 305.0, UPC 2006.
2. Keynote 10 on sheet a3 refers to scuppers; are you meaning to say "gutters"? Details 8 and 9, sheet a6, show a scupper: where does this occur? Reference: Section 103.2.3, UPC 2006.
05/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the submitted energy code calculations for the building envelope to coordinate with the building construction shown on the drawings. Roof 1 is shown as having R-30 batt insulation in the truss cavities not R-39 batt insulation (Details 8 & 9, sheet a6). Roof 2 is not shown as having any continuous insulation on the drawings. Exterior wall 2 is noted as having wood furring and R-10 batt insulation but the calculations claim metal furring with R-19 cavity insulation. The calculations also claim that exterior wall 2 has R-8 continuous insulation but it is not clear how that is being provided. None of the glazing is noted as having any particular U-value or SHGC requirements on the drawing. Reference: Section 104.2, International Energy Conservation Code 2006
2. Revise the energy code analysis, using the correct climate zone for Pima County < 4,000 feet. The town of Pima, Arizona is located northwest of Safford, Arizona. Reference: Section 302.2, IECC 2006, as amended by the City of Tucson.
05/05/2010 SEPTIC APPROVAL WWM REVIEW Denied need septic permit w/Pima County
NO SEPTIC RECORDS
05/10/2010 ANDREW CONNOR ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/06/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
07/06/2010 SUE REEVES REJECT SHELF Completed