Permit Number: T07CM03292
Parcel: 11518054A

Address:
710 W CARMEN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03292
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2010 SEPTIC APPROVAL WWM REVIEW Denied need septic permit w/Pima County
NO SEPTIC RECORDS
03/11/2010 RONALD BROWN ZONING HC REVIEW Approved
03/12/2010 ANDREW CONNOR ZONING REVIEW Denied 03/12/2010

Development Services Department
Landscape/Zoning Review Section

Andrew Connor

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may apply.
03/18/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Note: the drawings provided with this submittal are the same as those submitted and reviewed in July, 2009.

1. Fourth request, comment not addressed. Energy code calculations for the building envelope have not been provided; this is not the same as the Mechanical Compliance Certificate which has been provided. Reference: Section 101.4, International Energy Conservation Code 2006
2. Fourth request, comment not addressed. Revise the ductwork insulation (Mechanical Note 2.04) per Section 503.2.7, IECC 2006 unless the entire building has been designed per ASHRAE/IESNA Standard 90.1-2004. Reference: Section 501.2, IECC 2006, as amended by the City of Tucson. (See also item 7, Section 4 of the provided Mechanical Compliance Certificate.)
3. Third request, comment not addressed. Revise the ventilation calculations for AC-1 and AC-2 to include the required adjustments for spaces served by a common ventilation system. Reference: Section 403.3.2, IMC 2006.
4. Comment not addressed. Condensate drains may not terminate with a direct connection to a shower tailpiece. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson and Sections 311.4 and 807.2, UPC 2006.
03/19/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Note: the drawings provided with this submittal are the same as those submitted and reviewed in July, 2009.

1. Provide justification for not connecting the building sewer to the public sewer. Reference: Section 305.0, UPC 2006.
2. Comment not addressed. Clarify the size of the indirect drain from P-8; it is called out as 1" on sheet P3 and 2" on sheet P1 (keynote 11). Reference: Section 103.2.3, UPC 2006.
3. The design of the water heater has been changed but without a mounting height, it is still impossible to be sure that the routing of the T&P relief will meet the code requirements. Clarify how the temperature and pressure relief piping from the water heater is capable of day lighting not less than 6" above the finished grade without forming a trap. Reference Sections 103.2.3 and 608.5, UPC 2006.
4. The T&P relief for the water heater shall not be combined with the pan drain. Reference: Sections 310.1, 310.4, and 508.4, UPC 2006.
5. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
6. Coordinate the power requirements for the water heater with the electrical designer; the water heater is gas-fueled according to the electrical plans.
7. Sheet P3 shows what appears to be a scupper but no dimensions are shown. If no scupper is intended for this location above room 108, clarify how the cricket located on the roof prevents the accumulation of water. Reference: Sections 103.2.3 and 1106.0, UPC 2006.
8. Comment not addressed. Use Table 11-2 to size the horizontal rain leaders; the minimum horizontal leader size is 3". Reference: Section 1101.11.2.2.1, UPC 2006.
9. Comment not addressed. Clarify the proposed location of the downspouts for the gutters on the warehouse section of the building (i.e. no downspouts are shown). Reference: Section 103.2.3, UPC 2006.
10. Clarify how the accumulation of rainwater will be prevented on the south side of the building where the vaulted roof meets the west wall of room 100. Reference: Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/03/2010 DELMA ROBEY OUT TO CUSTOMER Completed
05/03/2010 SUE REEVES REJECT SHELF Completed