Permit Number: T07CM03292
Parcel: 11518054A

Address:
710 W CARMEN ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T07CM03292
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; Central District; 4,800 Square Feet of Warehouse; $3,818.07
08/13/2007 DAVE MANN FIRE REVIEW Approved
08/17/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied An approved site plan is required prior to building plan approval.
08/23/2007 HEATHER THRALL ZONING REVIEW Denied Zoning will continue with review of the building plans upon the resubmittal and once the structural review division has reviewed the plans.

Note that zoning will need the height from grade to finished floor.
08/29/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
2. Provide updated energy code compliance calculations. Reference Section 101.4, International Energy Conservation Code 2006
3. Provide the manufacturer's published equipment data along with mechanical and electrical operating information for the new HVAC equipment. Reference Section 301.6, IMC 2006.
4. Provide the heating and cooling calculations that were used to size the proposed HVAC equipment. Reference Section 312.1, IMC 2006.
5. Clarify the inclusion of EF-2, EF-3, EF-4, and EF-5 in the equipment schedule when they are not shown on the plans.
6. Show that the EF-1, with its pitched roof cap, is being installed in accordance with the conditions of its listing and the manufacturer's installation requirements. Reference Section 304.1, IMC 2006.
7. Show the size, routing, and termination of the condensate drains. Reference Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
8. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2006.
08/29/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
2. Provide approved justification for not connecting the building sewer to the public sewer from PDEQ. Reference Section 305.0, UPC 2006.
3. Coordinate the water service to the proposed building as shown on the site plan (AS1) and the plumbing plan (A8). (Note that Tucson Water does not provide either ¾" or 1-1/4" meters.)
4. Revise the water calculations to correspond to this project. The developed length of the water piping is much greater than 70 feet, the specified water closet requires a minimum pressure greater than 15 PSI, the pressure drop of a reduced pressure backflow preventer shall be included, and the static lift (elevation) from the water meter to the highest outlet shall be included. Reference Section 610.1, UPC 2006.
5. Include specifications for all of the plumbing fixtures being installed.
6. Clarify the specification of the lavatories (P-1): they are specified to be wall-hung but are shown as counter-mounted. Also, is the P-1 shown adjacent to the refrigerator and dishwasher the same as the P-1 lavatories? Reference Section 103.2.3, UPC 2006.
7. Finish the water isometric diagram to include the hot water piping, hot water return piping, and all of the pipe sizes. Reference section 103.2.3, UPC 2006.
8. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
9. Show that the shower control valve complies with the requirements of ASSE 1016. Reference Section 418.0, UPC 2006.
10. Provide combustion air openings for the water heater. Reference Section 507, UPC 2006.
11. Show that the size and termination of the gas vents complies with the requirements of Section 510.6, UPC 2006.
12. Show the route and termination of the temperature and pressure relief piping from the water heater. Reference Sections 103.2.3 and 608.5, UPC 2006.
13. Revise the drain piping sizes per Table 7-5, UPC 2006.
14. Provide upper terminal cleanouts (e.g. P-2 in the men's restroom) per Section 707.4, UPC 2006.
15. Provide additional cleanouts in drainage piping for aggregate horizontal changes in direction of 135 degrees. Reference Section 707.5, UPC 2006.
16. Provide the listing information for the 2-way cleanout shown at the junction of the building drain and the building sewer. Reference Sections 301.1.3 and 707.6, UPC 2006.
17. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006.
18. Revise the size of the branch gas piping to the water heater per Table 12-8, UPC 2006.
19. Provide roof drainage calculations and plans. Provide details for the scuppers. If the roof drains are to be used instead of scuppers, show the sizes of the drains and rain leader piping as well as the routing and termination of the leaders. Reference Section 1106.0, UPC 2006.
08/29/2007 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
09/10/2007 SEPTIC APPROVAL WWM REVIEW Denied need septic permit w/Pima County
09/12/2007 BROWN & ASSOCIATES BUILDING-COMMERCIAL REVIEW Denied September 10, 2007
James E. McMahon
6340 N. Campbell, #278
Tucson, AZ 85718
RE: EL CORONADO PLUMBING, STRUCTURAL AND ELECTRICAL REVIEW ONLY
ADDRESS: 710 W. CARMEN STREET
CITY OF TUCSON LOG NO.: T07CM03292
BROWN & ASSOCIATES PLAN CHECK NO: 85701-7011
REVIEWED TO: 2006 IBC, 2005 NEC
The first review comments in this letter require that the applicant respond with a detailed written
response to each comment indicating actions taken to resolve the comment issue. We request
that you provide reviewed and coordinated construction documents as applicable, highlighting
each change with a clouded or delta and a revision number on each drawing revised. This
review was limited to structural and electrical only and charged hourly for each review.
STRUCTURAL COMMENTS
Sheet S200
1. Per the architectural drawings, a storefront window occurs at south end. Revise
plans/details accordingly. Reference IBC Section 1603.
Sheet S300
1. Clarify how GLB frames into perpendicular GLB. Consider beam seat tab interference.
Reference IBC Section 1603.
Structural Calculations
Page 16
1. Check lintels for wind loads perpendicular to the lintel and provide bracing as/or needed.
Reference IBC Section 1604.
Page 22
1. Check opening jambs to support vertical/lateral loads. Reference IBC Section 1604.
ELECTRICAL COMMENTS
Sheet e1
1. Indicate all exit signs; i.e. lobby, warehouse hallways. Reference IBC Section 1011.1.
El Coronado Plumbing, Structural and Electrical Review Only
City of Tucson Log No: T07CM03292
September 10, 2007
Page 2
2. Provide a light switch for mechanical room. Reference NEC Article 210.70(C).
3. Provide egress lighting per IBC Section 1006.1.
Sheet e 2
1. Wire size appears to be undersized for AC1/AC. Clarify and revise plans as necessary
Ref. Reference NEC Table 310.16.
2. Spare breaker for circuits #2, 4 has no destination, clarify or remove. Reference NEC
Article 372.13.
3. Clarify wire going to sub-panel B from panel A, no wire in NEC table 310.16 matches
one line diagram. Reference NEC Article 310.16.
Brown & Associates contact information:
If you have any questions regarding resubmittal requirements or procedures please
contact Patti Schechter, Operations Manager at 480 991-3751.
If you have any questions or require additional clarification regarding these comments
please contact Larry Francis, Plans Examiner at 480 991-3751.
Sincerely,
BROWN & ASSOCIATES for CITY OF TUCSON
Michael J. Brown, C.B.O.
President
MB:ps
TU2 7011.1st Rev
09/12/2007 BROWN & ASSOCIATES ELECTRICAL-COMMERCIAL REVIEW Denied September 10, 2007
James E. McMahon
6340 N. Campbell, #278
Tucson, AZ 85718
RE: EL CORONADO PLUMBING, STRUCTURAL AND ELECTRICAL REVIEW ONLY
ADDRESS: 710 W. CARMEN STREET
CITY OF TUCSON LOG NO.: T07CM03292
BROWN & ASSOCIATES PLAN CHECK NO: 85701-7011
REVIEWED TO: 2006 IBC, 2005 NEC
The first review comments in this letter require that the applicant respond with a detailed written
response to each comment indicating actions taken to resolve the comment issue. We request
that you provide reviewed and coordinated construction documents as applicable, highlighting
each change with a clouded or delta and a revision number on each drawing revised. This
review was limited to structural and electrical only and charged hourly for each review.
STRUCTURAL COMMENTS
Sheet S200
1. Per the architectural drawings, a storefront window occurs at south end. Revise
plans/details accordingly. Reference IBC Section 1603.
Sheet S300
1. Clarify how GLB frames into perpendicular GLB. Consider beam seat tab interference.
Reference IBC Section 1603.
Structural Calculations
Page 16
1. Check lintels for wind loads perpendicular to the lintel and provide bracing as/or needed.
Reference IBC Section 1604.
Page 22
1. Check opening jambs to support vertical/lateral loads. Reference IBC Section 1604.
ELECTRICAL COMMENTS
Sheet e1
1. Indicate all exit signs; i.e. lobby, warehouse hallways. Reference IBC Section 1011.1.
El Coronado Plumbing, Structural and Electrical Review Only
City of Tucson Log No: T07CM03292
September 10, 2007
Page 2
2. Provide a light switch for mechanical room. Reference NEC Article 210.70(C).
3. Provide egress lighting per IBC Section 1006.1.
Sheet e 2
1. Wire size appears to be undersized for AC1/AC. Clarify and revise plans as necessary
Ref. Reference NEC Table 310.16.
2. Spare breaker for circuits #2, 4 has no destination, clarify or remove. Reference NEC
Article 372.13.
3. Clarify wire going to sub-panel B from panel A, no wire in NEC table 310.16 matches
one line diagram. Reference NEC Article 310.16.
Brown & Associates contact information:
If you have any questions regarding resubmittal requirements or procedures please
contact Patti Schechter, Operations Manager at 480 991-3751.
If you have any questions or require additional clarification regarding these comments
please contact Larry Francis, Plans Examiner at 480 991-3751.
Sincerely,
BROWN & ASSOCIATES for CITY OF TUCSON
Michael J. Brown, C.B.O.
President
MB:ps
TU2 7011.1st Rev

Final Status

Task End Date Reviewer's Name Type of Review Description
10/10/2007 THAUSER1 OUT TO CUSTOMER Completed
10/10/2007 THAUSER1 REJECT SHELF Completed