Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07CM03257
Parcel: 13104410A

Address:
5069 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03257
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2007 HEATHER THRALL ZONING REVIEW Approved
08/14/2007 LOREN MAKUS ENGINEERING REVIEW Approved
08/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03257 8/14/07

1. Electrical panel is existing according to Sheet A-1. Is new on Electrical plans. Please clarify.
2. HP-1 is existing according to Mechanical. Is new on Electrical plans. Please clarify.
3. Please note that City of Tucson currently enforces the 2006 IECC, not the 2003.
08/14/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
08/15/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/15/2007 CAGUILA1 MECHANICAL-COMMERCIAL REVIEW Needs Review
08/20/2007 ROBERT SHERRY WATER REVIEW Approved