Permit Number: T07CM03256
Parcel: 13104410A

Address:
5063 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03256
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2007 MARTIN BROWN FIRE REVIEW Approved
08/14/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations for mercantile occupancy.
08/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03256 8/14/07

1. Electrical panel is existing according to Sheets A-1 and M-1. Is new on Electrical plans. Please clarify.
2. HP-1 is existing according to Mechanical. Is new on Electrical plans. Please clarify.
3. Please note that City of Tucson currently enforces the 2006 IECC, not the 2003.
08/14/2007 ROBERT SHERRY WATER REVIEW Approved
08/14/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
08/14/2007 RSHERRY1 WWM REVIEW Passed
08/14/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/14/2007 LOREN MAKUS ENGINEERING REVIEW Approved
08/14/2007 HEATHER THRALL ZONING REVIEW Approved
08/15/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review