Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03256
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/14/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations for mercantile occupancy. |
| 08/14/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03256 8/14/07 1. Electrical panel is existing according to Sheets A-1 and M-1. Is new on Electrical plans. Please clarify. 2. HP-1 is existing according to Mechanical. Is new on Electrical plans. Please clarify. 3. Please note that City of Tucson currently enforces the 2006 IECC, not the 2003. |
| 08/14/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/14/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/14/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
| 08/14/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/14/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/14/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 08/15/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |