Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T07CM03249
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2007 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Approved | |
| 10/22/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/22/2007 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Completed | |
| 10/23/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/23/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/23/2007 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/29/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |