Permit Number: T07CM03219
Parcel: 13316024M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03219
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
08/06/2007 ROBERT SHERRY WATER REVIEW Approved
08/06/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/06/2007 MARTIN BROWN FIRE REVIEW Approved
08/06/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM03219 8/6/07

1. Ckt 2 shall take #10 conductor. Reference NEC 240.4 (D).
2. For service capacity of 720 amps, conductor would be 500 MCM, not 300.
3. It does not appear that there are 60' from the disconnect to the new panel.
08/06/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/07/2007 GERRY KOZIOL WWM REVIEW Approved
08/07/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed