Review Details: COMMERCIAL TI
Permit Number - T07CM03219
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/06/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/06/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/06/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/06/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM03219 8/6/07 1. Ckt 2 shall take #10 conductor. Reference NEC 240.4 (D). 2. For service capacity of 720 amps, conductor would be 500 MCM, not 300. 3. It does not appear that there are 60' from the disconnect to the new panel. |
| 08/06/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/07/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |