Permit Number: T07CM03219
Parcel: 13316024M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03219
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2007 STEVE SHIELDS ZONING REVIEW Approved
08/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to justify the use of 3 5-ton air conditioners for this tenant space.
2. Revise the termination of the condensate drains.
3. Provide the ventilation calculations.
4. Show the locations of all thermostats.
08/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03219 8/2/07

1. Demonstrate that the Insta-Hot is cord-connected to a standard duplex receptacle.
2. Insta-Hot power requirements call for 20A, which would be 2400VA, not 1500. A 25A or 30A circuit would also be adequate.
3. HP-2 and HP-3 appear to be switched on the Power Plan. Reference NEC 408.4.
4. Provide size of the overcurrent protection for Panel 130 feeder.
5. Provide fault calculations for new panel.
08/02/2007 ROBERT SHERRY WATER REVIEW Approved
08/02/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please revise the title to reference the scope of work as shell improvements per the submittal requirements for the City of Tucson.

2) Please revise the code references to the currently adopted codes per section 106.1.1 of the 2006 IBC (i.e. 2006 I-codes and ANSI 117.1-2003).

3) Please specify the rear water closet grab bar placement in relation to the side wall per section 604.5 of ANSI 117.1-2003.

4) Please be aware that the future tenant improvement may require additional plumbing fixtures in accordance with table 2902.1 of the 2006 IBC (i.e. drinking fountain, mop sink, separate sex restrooms, etc.).

5) Please provide verification that the lavatory in not within the required clear floor space in accordance with section 604.3.2 of ANSI 117.1-2003.

6) Please verify the height of the tile wainscot around the water closet in order to verify compliance with section 1210.2 of the 2006 IBC.

7) Please provide structural verification that the existing structural components can support the new mechanical units per section 106.1.1 of the 2006 IBC. In addition, please specify the weight of the new mechanical units on the plans per section 106.1.1.
08/02/2007 ANY ENGINEERING REVIEW Approved
08/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing fixtures required by Chapter 29, IBC 2006.
2. Show how the water temperature at the lavatory will be limited to 110 degrees Fahrenheit.
3. Limit the water pressure to no more than 80 PSI.
4. Lavatory faucets shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water or shall be designed to deliver no more than an average of one-half gallon of water per minute at a pressure of eighty PSI.
08/06/2007 CAGUILA1 WWM REVIEW Needs Review
08/06/2007 CAGUILA1 FIRE REVIEW Needs Review
08/06/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review