Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T07CM03216
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the mechanical drawing to clearly show how the work in the field has deviated from the approved plan . 2. Provide ventilation calculations for the A/C unit that is now serving the lunchroom. 3. The mechanical drawing revisions must be approved prior to receiving a final inspection approval. |
| 12/17/2007 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |