Review Details: REVISION - - 1ST
Permit Number - T07CM03216
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03216 12/6/07 1. Registrant shall sign and date seal on plans. 2. Lighting Fixture G is listed as 120V on Fixture Schedule. Powered at 277V. Please clarify. 3. Provide Mechanical Plans for verification of additional AC-14, and for approval by Mechanical Plans Examiner. 4. Have Permit Clerks add Mechanical and Plumbing to WorkFlow. |