Permit Number: T07CM03216
Parcel: 110162190

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03216
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2007 DAVE MANN FIRE REVIEW Approved
08/21/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied ELECTRICAL NOTES; PLEASE PROVIDE PANEL SCHEDULES FOR CIRCUITS INVOLVED,ALSO PROVIDE LOAD CACULATIONS FOR THESE PANELS.
RAY MAJUTA ,ELECTRICAL PLAN CHECK,8/21/07
09/07/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/13/2007 RSHERRY1 WWM REVIEW Passed
09/13/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the modifications to the gas piping system. Show the new piping and finish labeling the existing gas piping. Reference Section 103.2.3, UPC 2006.
09/13/2007 ROBERT SHERRY WATER REVIEW Approved
09/13/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the status of the A/C unit serving the remodeled area; is it new or existing? The notation in the gas calculations indicates that it may be new. If new, provide the electrical requirements, unit weight, and performance data. Reference Section 106.3.1, IMC 2006.
2. Provide a path for the return air from the vault room to the roof top unit.
3. Provide calculations to show compliance with the ventilation requirements per Section 403, IMC 2006.
4. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 503.2.8, IECC 2006.
5. Show the size, routing, and termination of the condensate drain for the A/C unit. Reference Section 307.2, IMC 2006 and Section 814.0, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2007 DELMA ROBEY OUT TO CUSTOMER Completed
09/17/2007 DELMA ROBEY REJECT SHELF Completed