Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03216
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/21/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | ELECTRICAL NOTES; PLEASE PROVIDE PANEL SCHEDULES FOR CIRCUITS INVOLVED,ALSO PROVIDE LOAD CACULATIONS FOR THESE PANELS. RAY MAJUTA ,ELECTRICAL PLAN CHECK,8/21/07 |
| 09/07/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/13/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
| 09/13/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the modifications to the gas piping system. Show the new piping and finish labeling the existing gas piping. Reference Section 103.2.3, UPC 2006. |
| 09/13/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/13/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the status of the A/C unit serving the remodeled area; is it new or existing? The notation in the gas calculations indicates that it may be new. If new, provide the electrical requirements, unit weight, and performance data. Reference Section 106.3.1, IMC 2006. 2. Provide a path for the return air from the vault room to the roof top unit. 3. Provide calculations to show compliance with the ventilation requirements per Section 403, IMC 2006. 4. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 503.2.8, IECC 2006. 5. Show the size, routing, and termination of the condensate drain for the A/C unit. Reference Section 307.2, IMC 2006 and Section 814.0, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/17/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 09/17/2007 | DELMA ROBEY | REJECT SHELF | Completed |