Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03208
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/02/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1. The proposed rooftop units weigh 1,015 pounds (without curb and accessories) but the structural drawings are based on an installed weight of only 800 pounds. Provide updated calculations to show that the roof structure provides adequate support. 2) Please revise the listed codes to the currently adopted codes for the City of Tucson (2006 I-codes, 2006 UPC, 2005 NEC, etc.). |
08/02/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The proposed rooftop units weigh 1,015 pounds (without curb and accessories) but the structural drawings are based on an installed weight of only 800 pounds. Provide updated calculations to show that the roof structure provides adequate support. 2. Provide load calculations to justify the use of two 10-ton units for the tenant space. |
08/02/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03208 8/2/07 1. It appears that Panel OW is existing. Please indicate so on the line diagram. 2. If the new panels are designated for future use, please mark them as such. Otherwise account for all electrical loads. 3. Provide fault current rating for new panels, and fault calculations as necessary. 4. Provide electrical requirements for the new AC unite. 5. Provide electrical circuit for new AC units, and electrical load calculations to tally up to service. 6. Provide a disconnecting means for new AC units per NEC 430 Part IX. |
08/02/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/02/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
08/02/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
08/03/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/03/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
08/20/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
08/20/2007 | PATRICIA GEHLEN | ZONING | REVIEW | Approved |