Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM03208
Parcel: 114600830

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03208
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1. The proposed rooftop units weigh 1,015 pounds (without curb and accessories) but the structural drawings are based on an installed weight of only 800 pounds. Provide updated calculations to show that the roof structure provides adequate support.

2) Please revise the listed codes to the currently adopted codes for the City of Tucson (2006 I-codes, 2006 UPC, 2005 NEC, etc.).
08/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The proposed rooftop units weigh 1,015 pounds (without curb and accessories) but the structural drawings are based on an installed weight of only 800 pounds. Provide updated calculations to show that the roof structure provides adequate support.
2. Provide load calculations to justify the use of two 10-ton units for the tenant space.
08/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03208 8/2/07

1. It appears that Panel OW is existing. Please indicate so on the line diagram.
2. If the new panels are designated for future use, please mark them as such. Otherwise account for all electrical loads.
3. Provide fault current rating for new panels, and fault calculations as necessary.
4. Provide electrical requirements for the new AC unite.
5. Provide electrical circuit for new AC units, and electrical load calculations to tally up to service.
6. Provide a disconnecting means for new AC units per NEC 430 Part IX.
08/02/2007 ROBERT SHERRY WATER REVIEW Approved
08/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/02/2007 LOREN MAKUS ENGINEERING REVIEW Approved
08/03/2007 MARTIN BROWN FIRE REVIEW Approved
08/03/2007 GERRY KOZIOL WWM REVIEW Approved
08/20/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/20/2007 PATRICIA GEHLEN ZONING REVIEW Approved