2406 E RIVER RD

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM03202
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2007 DAVE MANN FIRE REVIEW Approved
09/13/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please account for the 20W low voltage lamp on the lighting compliance table. This item was indicated in the Symbols list.
2. "D-1" or "D-2" are by each low voltage symbol on the plans. No Panel D this project. "D-2" is also used for a duplex receptacle, a different symbol on the list. Please clarify use of symbols and coordinate with panel designations on Sheet (unnumbered).
3. Provide a circuit for the pool lights. GFCI per NEC 680.23 (A) (3).
4. Provide a circuit for the entry fountain light. GFCI per NEC 680.51 (A) (3).
5. Provide GFCI protection for small fountain lights and large fountain lights.
09/13/2007 LINDA BUCZYNSKI BUILDING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
09/25/2007 GERARDO BONILLA REJECT SHELF Completed