Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM03200
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2007 GERRY KOZIOL WWM REVIEW Denied 1:GUEST HOUSE
2:NEEDS TO REVIEW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER (PUBLIC SEWER IN STREET, NOT IN ALLEY)
09/06/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity: T07CM03200
Date: 9/10/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

I. GENERAL REQUIREMENTS:
· Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
· Clarify all plan discrepancies:
· Ceiling insulation (min. R-30)
· Wall insulation
· Rafter sizes (min. 9½" cavity if batt insulation is used)
· Stud sizes
· Header sizes
· Electrical service size (amperes)
· Etc.
· Clarify electrical receptacle spacing (max 12' apart along walls, max 6' away from doors)
· Specify appliance circuit purpose
· Specify location of water line connection (tie-in at water meter?)

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2007 CINDY AGUILAR OUT TO CUSTOMER Completed