Permit Number: T07CM03174
Parcel: 121064130

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03174
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2007 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit evaluation
09/14/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T07CM03174

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

As of 6/12/2007 the City of Tucson has adopted the 2006 IRC with the exception of the plumbing portion which has been replaced with the 2006 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

SITE PLAN:

1. Indicate the location of sewer lines from property line to building, R106.1.1.
2. Show the water pipe size from the meter to the building. Show the point of connection for the proposed hot and cold branches. The pipe must be sized for the calculated load, 2006 UPC 610.1.

FOUNDATION PLANS:

1. Show or note (Detail C/4) a 6" minimum separation of untreated exterior posts or columns above finished grade, R319.1.4 exception 1.

FLOOR PLANS:

1. The Site Plan shows the new construction 3' from the Carport. Show compliance with R302.1 (City of Tucson Amended) by joining the roof structures.

SECTIONS - DETAILS:

1. Show a minimum 1" ventilation clearance between ceiling insulation and roof sheathing if insulation is attached to truss bottom cords and eave venting is used, R806.3. This may be accomplished w/ baffles.

PLUMBING PLANS:

1. The City of Tucson has adopted the 2006 Uniform Plumbing Code with state amendments. The plans (Plumbing Fixture Schedule) should reference this code, or appeal to the Building Official for IRC design approval.
2. Provide a fixture unit schedule (include dishwasher) UPC Tables 6-4 & 7-3.

MECHANICAL PLANS:

1. The furnace shows a fresh air kit. Therefore, note that air inlets shall be located a minimum of 10' from vent openings or exhaust outlets unless the outlet is 3 feet above the air inlet (if applicable), M1602.2.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review