Permit Number: T07CM03166
Parcel: 12514006A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03166
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the extent of work in "Suite 704".
08/29/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
2. Finish drawing the water riser diagram. Indicate how the pipe sizes were determined. Reference section 610.1, UPC 2006.
3. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). Reference Section 402.1, UPC 2006, as amended by the City of Tucson.
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2006 and Section 504.3, IECC 2006.
5. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2006.
6. Clarify the greywater system noted on sheet PS1.
08/29/2007 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
09/05/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved