Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the balancing data for the hood and MUA unit per the hood manufacturer's listing information. Reference Section 508.2, IMC 2006.
2. Show how the make up air not provided by the MUA unit is to be supplied to the room (i.e. show the source of outside air to be transferred into the kitchen).
Reference Section 508.1, IMC 2006.