Permit Number - T07CM03158
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the drawings; clarify the type of fan to be used, the design of the MUA unit, and how the make up air is to be introduced into the room. 2. Show how the water supply and drain are to be handled for the MUA unit. 3. Clarify the balancing data for the MUA unit. 4. Show the size of the exhaust duct. |
| 08/10/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/24/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | IN THE LOAD CALCULATIOS FOR THE REPLACEMENT HOOD AND FAN, INCLUDE THE WORKING WEIGHT OF MAINTENANCE PERSONEL (150LB) . IMC 506 |