Permit Number: T07CM03158
Parcel: 12317201H

Address:
1420 N VINE AV

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM03158
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the drawings; clarify the type of fan to be used, the design of the MUA unit, and how the make up air is to be introduced into the room.
2. Show how the water supply and drain are to be handled for the MUA unit.
3. Clarify the balancing data for the MUA unit.
4. Show the size of the exhaust duct.
08/10/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/24/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied IN THE LOAD CALCULATIOS FOR THE REPLACEMENT HOOD AND FAN, INCLUDE THE WORKING WEIGHT OF MAINTENANCE PERSONEL (150LB) . IMC 506

Final Status

Task End Date Reviewer's Name Type of Review Description
08/24/2007 DELMA ROBEY APPROVAL SHELF Completed
08/24/2007 DELMA ROBEY OUT TO CUSTOMER Completed
08/24/2007 DELMA ROBEY REJECT SHELF Completed