Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM03158
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/27/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PLEASE USE 1/8" FONT FOR DETAILS 2. YOU MAY NOT USE COMBUSTIBLE FRAMING BEHIND HOOD (REF 2006 IMC) |
| 07/27/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the hood connection detail to eliminate any combustible structural members within 18" of the grease duct. Reference Section 506.3.6, IMC 2006. 2. Show how the hood system complies with Section 507.2.1.1, IMC 2006. 3. Clarify the balancing data for the hood and MUA unit per the hood manufacturer's listing information. Reference Section 508.2, IMC 2006. 4. Show how the make up air not provided by the MUA unit is to be supplied to the room. Reference Section 508.1, IMC 2006. |
| 07/27/2007 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/10/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |