Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1. PLEASE USE 1/8" FONT FOR DETAILS

2. YOU MAY NOT USE COMBUSTIBLE FRAMING BEHIND HOOD (REF 2006 IMC)
07/27/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the hood connection detail to eliminate any combustible structural members within 18" of the grease duct. Reference Section 506.3.6, IMC 2006.
2. Show how the hood system complies with Section 507.2.1.1, IMC 2006.
3. Clarify the balancing data for the hood and MUA unit per the hood manufacturer's listing information. Reference Section 508.2, IMC 2006.
4. Show how the make up air not provided by the MUA unit is to be supplied to the room. Reference Section 508.1, IMC 2006.
07/27/2007 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2007 VFLORES1 OUT TO CUSTOMER Completed