Permit Number: T07CM03148
Parcel: 138181420

Address:
9 E ELVADO RD

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T07CM03148
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2008 GERRY KOZIOL WWM REVIEW Approved
01/23/2008 LOREN MAKUS ENGINEERING REVIEW Denied A floodplain use permit must be approved before this plan can be approved.
02/04/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 2/05/08
Activity: T07CM03148
Address: 9 E. Elvado Rd.
Applicant: Roberto Otriz

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.
3. Provide sheet number 8 or correct page number references.
4. As of 6/12/2007 the City of Tucson has adopted the 2006 IRC. All plans should reference this code or appeal to the Building Official for 2003 design approval.

STRUCTURAL PLANS:
5. Justify beam size at patio.
6. Justify rafter size at master bedroom.
7. Justify existing 4x8 beam at master bedroom.
8. Specify weight and ICBO# of concrete or clay-type roofing and clarify design criteria.

ELECTRICAL PLAN:
9. Provide circuit number references for all lighting and receptacle outlets.

PLUMBING PLAN:
10. Provide the maximum developed length of water line from the meter the furthest appliance served, and the diameter of the water service line, UPC Table 6-6.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2008 DELMA ROBEY APPROVAL SHELF Completed
02/12/2008 DELMA ROBEY OUT TO CUSTOMER Completed
02/12/2008 DELMA ROBEY REJECT SHELF Completed