Permit Number: T07CM03138
Parcel: 10512024D

Address:
4070 N ORACLE RD

Review Status: Active

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03138
Review Name: POST 3RD PARTY REVIEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2007 ROBERT SHERRY WATER REVIEW Denied 1. Reduced pressure backflow prevention assemblies shall not be installed in locations inaccessible to Tucson Water. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Clarify the intent of detail 6/MP-2.1 and coordinate with detail 2/MP-2 with respect to the backflow prevention device being specified. A reduced pressure zone backflow prevention assembly is required to be installed immediately downstream of the water meter (the addition of an additional double check valve assembly is not a code requirement). Also, the pressure drop associated with a reduced pressure zone backflow prevention assembly is much higher than the 4-PSI noted in the submitted water pressure calculations.
09/07/2007 MARTIN BROWN FIRE REVIEW Approved
09/10/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied Provide two copies of the approved development plan, landscape and NPPO plans with the approved building plan set. A site application card (yellow card) with the CDRC approved development plan must be stamped with signatures for DSD site approval by the following reviewing sections; Fire, Zoning, Handi-cap, Engineering, Plumbing and Landscape/NPPO. The development plan may be walked through for stamps and site card sign off. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan.
09/13/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; Central District; 22,189 Square Feet of Retail Space; $34,016.03
09/18/2007 GERRY KOZIOL WWM REVIEW Denied NEEDS TO SHOW LOCATION AND METHOD OF CONNECTION TO PUBLIC SEWER
09/24/2007 TERRY STEVENS ZONING REVIEW Denied 09/24/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2007 ANY REJECT SHELF RECEIVED