Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM03137
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/03/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how often the temperature limit stop on the lavatory faucet is to be adjusted to guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Show that the branch water piping sizes called out for the flush valves (P-2 and P-3) will not result in water velocities greater than 8 FPS. Reference: Section A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 3. Provide a floor drain adjacent to the 3-compartment sink (P-5) per Section 704.3, UPC 2006. 4. Provide a vent to protect the grease trap from siphonage and back-pressure. Reference: Sections 1002.1 and 1014.2.3, UPC 2006. 5. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices (e.g. grease interceptors) that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area. |
| 04/11/2008 | CPIERCE1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/11/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |