Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03137
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/27/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/27/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/27/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/27/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/27/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/27/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 07/27/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the water pressure calculations to show how the friction loss per 100 feet was obtained. 2. Revise the water pipe sizes to account for the use of water closets with flush valves. 3. Show the sizes of the water meter and the reduced pressure backflow preventer at the meter. 4. Provide a means for protecting the traps of the floor drains. 5. Provide water hammer arrestors. 6. Specify the floor sink. |
| 08/01/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 08/01/2007 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 08/01/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |