Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03133
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/26/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/26/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font to be a minimum of 1/8", all upper case. 2. Show how the water heater is to connected to the building structure. 3. Specify the material to be used for the RO water piping. 4. Clarify the venting arrangment near P-3; VTR or connect to other vents overhead? 5. The drain from a humidifier shall drain to an indirect waste receptor with an air gap. Reference Section 807.1, UPC 2006. |
| 07/26/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide backflow protection for the reverse osmosis filter. 2. Revise the font size to a minimum of 1/8", all upper case. 3. Provide calculations and show how the new equipment is to be supported on the roof or supported from the walls or ceiling. |
| 07/26/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/26/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/26/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 07/26/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/31/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Please provide the Water Heater a disconnecting means according to NEC Article 422 Part III. 2. Circuits L-10 and L-12 run together on the Lighting Plan. Please clarify. 3. Lighting Fixture Schedule and email reply indicate exterior lighting. Such lighting does not show up on the plot, nor does the compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. |
| 08/14/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 08/14/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/14/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 08/14/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/14/2007 | DELMA ROBEY | REJECT SHELF | Completed |