Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM03118
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03118 11/30/07 1. Document full power requirements for additional water heater on plans. 2. Indicate size of conductors for additional water heater. 3. Water heater 2-pole CB has been superimposed with server 3-pole CB. Regerence Ckt G3-37,39,41 and Ckt G3-39,41. 4. Please have the Registered Electrical Engineer on this project provide and seal the updated and complete panel schedule with load tabulation, including the 25% demand factor for any continuous loads. |
| 11/30/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |