Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM03118
Parcel: 11445262J

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM03118
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/30/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03118 11/30/07

1. Document full power requirements for additional water heater on plans.
2. Indicate size of conductors for additional water heater.
3. Water heater 2-pole CB has been superimposed with server 3-pole CB. Regerence Ckt G3-37,39,41 and Ckt G3-39,41.
4. Please have the Registered Electrical Engineer on this project provide and seal the updated and complete panel schedule with load tabulation, including the 25% demand factor for any continuous loads.