Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM03105
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/27/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 08/27/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide fire resistance ratings per table 602 of the 2006 IBC or locate container a minimum of 10' from the property lines. 2. Provide manufacturers information on construction of container. eg: allowable dead loads, live loads, etc. |
| 08/27/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | INFORMATION REQUESTED NOT PROVIDED |
| 08/27/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | DISCUSSED ISSUE RELATED TO MANUFACTURES DESIGN SPECIFICATIONS WITH LEERAY. DECISED IT WAS NOT AN ISSUE AT THIS TIME. |
| 09/17/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/17/2007 | DAVID RIVERA | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/17/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |