Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM03094
Parcel: 126042730

Address:
1034 N JERRIE AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T07CM03094
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2007 DAVE MANN FIRE REVIEW Denied Additional hydrant or fire sprinklers required. Please refer to C.O.T. amendments to the 2006 International Fire Code (section 508) for location requirements.
10/25/2007 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments
10/25/2007 TERRY STEVENS ZONING REVIEW Denied TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: T07CM03094
1034 N. Jerrie Ave.
Site Plan

TRANSMITTAL: 10/25/07

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. DS 2-02.2.1.8 Per IBC Sec. 1106.5 One van accessible handicap parking space is required for every six or fraction thereof provided handicap parking spaces. The provided handicap parking space is not a van accessible parking space. An 8' wide access aisle with an 8' wide parking space is required or an 11' wide parking space with a 5' access aisle . Revise plan and detail 9 of C1.2.

2. Keynote #12 indicates a 12x35 loading zone, the plan indicates a 10x18. Revise note.

In the land use requirements block on page C1.0 the code section and the size of the loading zone are incorrect. Revise.

3. Provide 2 cpoies of the site plan for approval.

4. The above comments are minor in nature and can be reviewed over the counter by setting an appointment with me.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\zoning\siteplan\DSC\T07CM03094-2.doc
11/01/2007 ANDREW CONNOR LANDSCAPE REVIEW Approved
11/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Backflow prevention assemblies shall be located as close as practicable to the service connection and in accordance with the manufacturer's specifications and Tucson Water's standard installation details. Reference Chapter 27, Article V, Section 27-76 (a), Tucson Code. http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Note: A 5/8" water meter is limited to demands of 10 GPM or less. If only the minimum plumbing fixtures required by Table 2902.1 (Business Occupancy) are to be installed, a 5/8" meter will be adequate. Should additional plumbing fixtures be proposed, a larger water meter may be required.
11/23/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: November23rd, 2007
ACTIVITY NUMBER: T07CM03094
PROJECT NAME: Jerrie Rig
PROJECT ADDRESS: 1034 North Jerrie Avenue
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.


RESUBMITTAL REQUIRED: SITE PLAN


1. A grading plan will be required for this project. At the time of the next submittal submit a completed grading application to formally start the review process for grading. DS 2-02.2.1.A.17.

2. The refuse container location as indicated on the site plan cannot be located at the back of the required back up spur. Revise the site plan to show the refuse container in a different location. Refer to Development Standard 6-01 for commercial requirements. Show vehicle maneuverability. DS 2-02.2.1.32

The above comment is from the previous review. For the current proposal of the vehicle backing up more than 40', a Development Standard Modification Request (DSMR) will be required. Contact the CDRC office for the submittal process. Contact Loren Makus for any questions at 837.4927.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/26/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
11/26/2007 GERARDO BONILLA REJECT SHELF Completed