Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM03094
Parcel: 126042730

Address:
1034 N JERRIE AV

Review Status: Completed

Review Details: SITE

Permit Number - T07CM03094
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2007 DAVE MANN FIRE REVIEW Denied Please provide location of nearest fire hydrant. Include dimensions to property line. C.O.T amendments to the 2006 IFC (section 508) limit the distance buildings can be away from hydrants.
07/31/2007 TERRY STEVENS ZONING REVIEW Denied TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: T07CM03094
1034 N. Jerrie Ave.
Site Plan

TRANSMITTAL: 08/02/07

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-02.2.1.7 The indicated allowed/required setback for the west setback is not correct. Per LUC Sec. 3.2.6.5 the required setback is 20' or 1 ½ times the height of the structure whichever is greater. Revise note.

2. DS 2-02.2.1.8 On detail 9 sheet C1.2, clearly indicate the required maximum slope for the handicap parking space and access aisle per ANSI 117.1-2003 Sec. 502.5. (max. 1:48 slope)

3. DS 2-02.2.1.9 Per DS 2-09.4.1, class 2 bicycle parking spaces are to be located no more than 50' from the main building entrance. Clearly indicate the location of the main entrance of the building on the site plan.

4. DS 2-02.2.1.11 See DS 3-05.2.2.D for design criteria regarding the required back up spur located near the north east corner of the property. As shown the backup spur does not meet the minimum requirements of 3' radius, 24' width, and minimum of 3' clear area behind the backup spur. The trash enclosure will not be allowed to be located at the backup spur as indicated on the site plan.

5. DS 2-02.2.1.12 The truncated domes indicated on the site plan and detail 9 of sheet C1.2 are located in the wrong location. They are to be located on the landing, across the full width the access aisle to a depth of 24". Truncated domes are also required on the handicap ramps located in the right of way. See engineering comments.

6. DS 2-02.2.1.13 If applicable, provide the location, type, size and height of existing and proposed signage.

7. DS 2-02.2.1.14 Clearly demonstrate maneuverability for the loading zone. See engineering comments.

FYI: There has been a change to the requirements for loading zones in the LUC. LUC Sec. 3.4.5 has been revised in order to provide a smaller loading zone for some uses. The changes to the LUC are available on line. For this project a review of the new loading zone requirements might be a help. In Commercial Services Use Group, Administrative and Professional Office Sec. 3.4.5.6 can be used if the building is less than 5000 sq. ft. This allows a 10X18 loading zone with less restrictive screening possible.

8. DS 2-02.2.1.28 Darken the surrounding zoning callouts for the adjacent properties to a legible line weight.

9. DS 2-02.2.1.32 The refuse container location as indicated on the site plan cannot be located at the back of the required back up spur.

10. DS 2-02.2.2.A.2 Provide on the site plan, dimensions for the foot print of the proposed structure.

11. Depending on responses to the above comments and changes to the site plan, further comments may be forth coming.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\zoning\siteplan\DSC\T07CM03094.doc
08/02/2007 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning commetns
08/08/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Revise the landscape and site plans to show the locations and note the height and materials used to construct any proposed or required screen walls. DS 2-07.A.3.

2. A 30" continuous screen along street frontages for vehicle use area must be provided per LUC Table 3.7.2-I

3. A 5' wall is required to screen office zoned properties from vehicle use area per LUC Table 3.7.2-I.

4. A 6' wall is required to screen loading zone from Jerrie Ave per LUC Table 3.7.2-I.

5. Vegetation or structures higher than thirty (30) inches must be located outside of the sight visibility triangle. Show required sight visibility triangles on the landscape plan (Sheet L1).

6. Include inside dimensions of strip planter within vehicle use area on the landscape, site and grading plans. A minimum of 4' in width must be provided for each canopy tree. The measurement is always within the planter area and does not include any material which defines the outer edge of the unpaved area per DS 2-06.3.3.C. Include dimensions on the site and landscape plans.

7. All landscape areas will be depressed to accept water flow from roofs, PAAL, and parking areas. Show by detail or spot elevations how landscape areas will accommodate water harvesting.

8. Note: The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.
08/08/2007 ANDREW CONNOR NPPO REVIEW Approved Exception
08/19/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: August 21, 2007
ACTIVITY NUMBER: T07CM03094
PROJECT NAME: Jerrie Rig
PROJECT ADDRESS: 1034 North Jerrie Avenue
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

1. Remove the shading from the asphalt area. The shading decreases the legibility of the plan after microfilming.

2. Indicate the width of the sidewalk in cross section B/C1.1. DS 2-02.2.1.A.12.

3. Indicate in keynote 10 the width of the sidewalk. All new development is to provide 5' sidewalks within the ROW. DS 2-02.2.1.A.12.

4. A grading plan will be required for this project. At the time of the second submittal submit a completed grading application to formally start the review process for grading. DS 2-02.2.1.A.17.

5. The backup spur does not meet the minimum requirements of 3' radius, 24' width, and minimum of 3' clear area behind the backup spur. Revise the site plan to meet the minimum requirements of DS 3-05.2.2.D. DS 2-02.2.1.A.11.

6. The truncated domes indicated on the site plan and detail 9 of sheet C1.2 are located in the wrong location. All accessible curb ramps shall have truncated domes installed that shall be twenty-four (24) inches minimum in the direction of travel and extend the full width of the curb ramp or flush surface. The domes shall be located so the edge nearest the curb line is six (6) inches to eight (8) inches from the curb line. ANSI 406.12, ANSI 705

7. Show the loading vehicle maneuverability for the required loading space. The minimum requirements for a 30' single unit vehicle is an outside radius of 42' and inside radius of 28'. American Association of State Highway and Transportation Officials.

8. All easements affecting the property must be graphically shown on the site plan with docket and page. Keynote 27 depicts a power pole to remain; show the easement information on the plan. DS 2-02.2.1.A.20.

9. From the street centerline of Jerrie Avenue dimension to the proposed sidewalk. DS 2-02.2.1.A.21.

10. The refuse container location as indicated on the site plan cannot be located at the back of the required back up spur. Revise the site plan to show the refuse container in a different location. Refer to Development Standard 6-01 for commercial requirements. Show vehicle maneuverability. DS 2-02.2.1.32

11. Please note that subsequent comments may be necessary upon resubmittal, depending on the nature and extent of revisions that occur to the plans.
08/20/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanouts for the building sewer at intervals no longer than 100 feet. Reference Section 719.0, UPC 2006.
2. Revise the site drawing to show the location and size of the reduced pressure backflow preventer assembly and the size of the existing water meter. Reference Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/17/2007 DELMA ROBEY OUT TO CUSTOMER Completed
10/17/2007 DELMA ROBEY REJECT SHELF Completed