Permit Number: T07CM03088
Parcel: 127110640

Address:
6015 E 5TH ST

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM03088
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please revise the font size on the plans to a minimum of 1/8" and all capital letters in accordance with the submittal requriements of the City of Tucson.

2) Please revise the codes under which the design was completed to the 2006 IBC as adopted by the City of Tucson. Projects submitted after July 13, 2007 must comply with the 2006 I-codes.

3) Please provide structural calculations for the structure per section 106.1.1 of the 2006 IBC.

4) Please denote the proximity of the carport foundation system to the existing structure and verify that the stormwater removal and structural aspects comply with the applicable codes per section 106.1.1 of the 2003 IBC.