| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/23/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 07/23/2007 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 07/23/2007 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Approved | |
| 07/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM03086 7/23/07 1. May not parallel conductors smaller than 1/0. Reference NEC 310.4. They are not all in the same raceway per NEC 300.3 (A) (1). 2. If the landing lugs are not listed for double-termination, the above would not be Code-compliant either. |