Permit Number: T07CM03086
Parcel: 123031090

Address:
2732 E LEE ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING-WALKTHRU

Permit Number - T07CM03086
Review Name: RESIDENTIAL BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2007 STEVE SHIELDS ZONING REVIEW Approved
07/23/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/23/2007 SSHIELD1 NPPO REVIEW Passed
07/23/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved
07/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM03086 7/23/07

1. May not parallel conductors smaller than 1/0. Reference NEC 310.4. They are not all in the same raceway per NEC 300.3 (A) (1).
2. If the landing lugs are not listed for double-termination, the above would not be Code-compliant either.