Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03057
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/02/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The revision to detail F/A301 shows an overflow scupper that requires a minimum accumulation of 4" of water on the roof at the drain location before the overflow scupper starts to flow. Provide structural calculations to show that the roof is capable of supporting the additional rain load. Reference: Sections 1101.11.1 and 1101.11.2.1, UPC 2003, and Section 1611.1, IBC 2003. |
10/02/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The areas used to calculate the outside air for the auditorium (for AC-1, AC-2, and AC-3) appear to be about 20% lower than the total auditorium area derived from the architectural floor plan. 2. Justify the use of a "hotel lobby" for the outside air calculation for AC-4 as compared to a "public assembly space lobby" based on Table 6-1, ASHRAE Standard 62.1-2004. 3. The use of Section 403.3.2, IMC 2003 to determine to required ventilation for a common ventilation system is valid only if the outside air requirements for each zone have been calculated using Section 403.3, IMC 2003, IMC 2003. If ASHRAE Standard 62.1-2004 has been used to determine the required amount of outside air for a system, Section 6.2.5.1 of ASHRAE Standard 62.1-2004, shall be used. Reference: Section 403.3, IMC 2003, as adopted by the City of Tucson. 4. Sheet M101 has been printed with the background too faint to be seen. Please reprint this sheet. Reference: Section 106.3.1, IMC 2003 |
10/06/2008 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/08/2008 | SUE REEVES | OUT TO CUSTOMER | Completed |
10/08/2008 | SUE REEVES | REJECT SHELF | Completed |