Permit Number: T07CM03057
Parcel: 132166420

Address:
817 E OHIO ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T07CM03057
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2008 RONALD BROWN ZONING HC SITE REVIEW Denied PERTAINING TO THE PREVIOUS COMMENT CONCERNING DETAIL "D" PAGE 4, WHICH IS REFERENCED TO AND DUPLICATED FOR 6 RAMPS SHOWN ON THE SITE PLAN, PAGE 2:
1. AS PER NOTE 5 SHEET 2, IT REFERENCES DETAIL D/4 AS A DS 207 STANDARD DETAIL. DS 207 IS A COT DOT DETAIL FOR PUBLIC R.O.W. CONSTRUCTION USE ONLY, NOT FOR PRIVATE PROPERTY. DS 207 HAS NO CONFIGURATION AS DEPECTED BY DETAIL D/4.
2. THE GOVERNING ACCESSIBIOLITY CODE FOR PRIVATE PROPERTY IS THE 2006 IBC, CHAPTER 11 AND ICC 117.1. PLEASE CLARIFY IN THE 2006 IBC/ICC 117.1 WHERE THIS RAMP CONFIGURATION IS DETAILED AND APPROVED?
3. PLEASE CALRIFY HOW THIS CONFIGURATION WORKS.
07/17/2008 TERRY STEVENS ZONING REVIEW Approved
07/25/2008 PETER MCLAUGHLIN NPPO REVIEW Approved
07/25/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. Per LUC 3.7.2.7 indicate surface treatment within adjacent right-of-way areas either on the landscape plan drawing or in general note 8 on sheet 1 of 5.

2. Provide a list of the drought tolerant seeds to be used in the areas proposed for hydro-seeding. Refer to DS 2-16 for criteria and guidelines and to the drought tolerant plant seed list prepared for use within the Tucson Active Management Area by the Arizona Department of Water Resources. DS 2-16.2.1.B
08/06/2008 LOREN MAKUS ENGINEERING REVIEW Denied August 6, 2008
T07CM03057 and T07BU01542
Site and Grading Plan Review

The Site and Grading Plans cannot be approved at this time. Address the following comments and submit a revised site plan for review. Include a letter that details how each comment has been addressed.


Site Plan/Grading Plan Comments:

1. The SWPPP will be approved when the grading plan is approved. Revise the SWPPP as necessary if the site and grading plans are revised. Include the SWPPPs with the next submittal.
2. Clarify the curb ramps and the detail used for them. The curb ramps key note (KN 5) all refer to the same detail (D/4), but represent different configurations.

I am willing to meet with you to approve the revision over-the counter. If you wish to exercise this option, please contact me to set up an appointment.
If you have any questions or wish to set up a meeting, I can be reached at 520.837.4927 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate