Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2007 DAVE MANN FIRE REVIEW Approved
07/19/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/03/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please revise all code references to the currently adopted codes for the City of Tucson (2006 I-codes, 2006 IECC, ANSI 117.1-2003, etc.).

2) Please verify if the supply fan is new or existing per section 106.1.1 of the 2006 IBC. If the unit is new, please provide verification that the existing structural can support the new loads.
08/09/2007 ROBERT SHERRY WATER REVIEW Approved
08/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide sufficient information to evaluate the revised natural gas piping system, including the total connected load for the gas meter along with the developed length to each load. Reference Section 1209.1, UPC 2003.
2. Clarify the accessibility of the shut off valve located near the connection of the new 3" gas piping to the existing 4" gas piping. Reference Section 103.2.3, UPC 2003.
3. Relocate the point of connection of the gas supply to the emergency generator to the supply side of the main building shutoff valve. Reference Section 7.9.7, NFPA 110-2005.
08/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Available fault current at the new transfer switch and new Panel E. Existing service switchboard is very close, and this does not appear to be addressed on the plans. Ideally the exact ratings should be provided on the plans so the Contractor and our Inspectors have no question.

2. Loading of Panel E and its feeder. It comes out to about 99A as calculated on the plans, and is on a 100A circuit. Since the basis for the calculation is a 1968 "Asbuilt", even the 25% safety factor may not be reliable. Unfortunately, I have seen City panels that did not even have that much correspondence between the plans, the field documentation, and actual installed loads. Didn't know exactly how I would call this until I noticed how close we were to the 100A circuit rating. COMMENT SATISFIED REFERENCE TELEPHONE CONVERSATION WITH ANDY BROTHERS 8/13/07.

3. The circuit breakers on the generator terminals. Would like to discuss. COMMENT SATISFIED REFERENCE TELEPHONE CONVERSATION WITH ANDY BROTHERS 8/13/07.
08/09/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the gas train complies with the requirements of Section 5.2, NFPA 37-2002 (e.g. manual leak test valve). Reference Section 915.1, IMC 2003.
08/14/2007 RSHERRY1 WWM REVIEW Passed