Permit Number: T07CM03043
Parcel: 115180050

Address:
1601 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T07CM03043
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2008 ANDREW CONNOR LANDSCAPE REVIEW Denied Submit the last approved and stamped site and landscape plans to verify existing (as built) site conditions.
03/31/2008 RBROWN1 ZONING HC SITE REVIEW Denied 1. PARKING SHOWN 219, ACCESSIBLE SPACES REQUIRED 7, SPACES PROVIDED 9 ACCESSIBLE PLUS 2 VAN ACCESSIBLE, 2006 IBC, SECTION 1106
2. AT MAIN BUILDING NORTH ENTRANCE, PROVIDE A CONCRETE SIDEWALK RAMP IN LIEU OF A PARKING SPACE RAMP, ANSI 117.1, SECTION 406
3. SHOW ACESSIBLE ROUTE FROM PUBLIC R.O.W.TO FRONT ENTRANCE, 2006 IBC, SECTION 1104.1
4. SHOW ACESSIBLE ROUTE THROUGH ENTIRE COMPLEX.
5. FOR ALL ACCESSIBLE ROUTES, SHOW SPOT GRADES TO CONFIRM THAT SLOPES MEET ANSI 117.1 REQUIREMENTS, SECTIONS 405
6. JUSTIFY ACCESSIBLE PARKING GROUPING AND DISTRIBUTION THROUGH OUT SITE IN REFERENCE TO COMPLIANCE WITH 2006 IBC, 1106.6
7. SHOW SIDEWALK RAMPS AT ALL ACCESSIBLE PARKING ISLES, ANSI 117.1, SECTION 406
8. PROVIDE SWIMMING POOL CONCRETE RAMP DETAILS
AS PER ANSI SECTION 405
9. INSURE ACCESSIBILITY FOR ALL CARD ACCESS DEVICES
10. SET ALL ACCESSIBLE PARKING SIGNS BACK TO SIDEWALK CURB NOT FLUSH WITH WHEEL STOP
11. PROVIDE DETECTABLE WARNINGS CURB RAMPS AND MARKED PEDESTRIAN CROSSINGS ANSI 117.1, SECTION 406.12, .13 AND .14
03/31/2008 DAVID RIVERA ZONING REVIEW Denied 1. The as built site plan was approved July 2007. Submit a copy of the JUly 2007 approved and stamped site plan for reference.

2. List the number of units.

3. Handicapped review will be adressed by Ron Brown Commercial Plans Reviewer. See his comments related to ADA/HC review.
04/22/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied Provide copy of last approved site plan for re-stamp.

Bianca Ramirez