Permit Number: T07CM03043
Parcel: 115180050

Address:
1601 N ORACLE RD

Review Status: Completed

Review Details: SITE

Permit Number - T07CM03043
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2007 MARTIN BROWN FIRE REVIEW Denied Please indicate location of fire hydrants
All access road less then 36 feet shall have fire lane signs posted per IFC Appendix D (city modifications)
All gates shall follow the fire code requirements sec IFC 503.6.1 & 503.6.2 Gates (city modifications).
All gates shall be on the Fire Department key system.
08/07/2007 ANDREW CONNOR LANDSCAPE REVIEW Passed
08/08/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved This is for an as built site plan approval only. Approval of this site plan is not for the intent to construct. There is no site construction taking place, therefore a floodplain use permit is not required. This project currently has 9 buildings under construction for tenant improvement permits, floodplain use permits accompany each building permit.
08/08/2007 ANDREW CONNOR NPPO REVIEW Passed
08/13/2007 SREEVES1 ADA REVIEW Passed not a COT project
08/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the first floor elevations for the buildings. Reference Section 103.2.3, UPC 2006
2. Revise the site drawing to include the following information:
a. the location of the main water lines and fire hydrants
b. the location of any gas meters
c. the location and size of the public sanitary sewer
d. the location, invert, and rim elevation of all manholes and cleanouts
Reference City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006.
08/23/2007 DAVID RIVERA ZONING HC SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2007 GERARDO BONILLA OUT TO CUSTOMER Completed