Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM03033
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | 1:PARKING GARAGE @ MLK DEPOT PLAZA-ALL DISCHARGES TO GROUND- NO GARAGE DRAIN PLUMBING TO BE CONNECTED TO PUBLIC SEWER. 2:NEED TO PERMIT 8" PRIVATE SEWER PER DOWL DRAWING C1.1 FOR FUTURE BLDG PADS "A" & "B". NEEDS DEQ REVIEW & APPROVAL IF OVER 3000 GAL/DAY NEEDS MANHOLE TAP CONSTRUCTION PERMIT (8TH FLOOR REVIEW/5TH FLOOR PERMMIT) |
| 01/09/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/21/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/21/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 12/21/2007 | DAVE MANN | FIRE | REVIEW | Denied | On Sheet A0.02 It indicates a NFPA13R sprinkler system will be used. This building has too may stories. Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. NFPA 13 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. |
| 12/24/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/22/2008 | THAUSER1 | OUT TO CUSTOMER | Completed |
| 01/22/2008 | SUE REEVES | REJECT SHELF | Completed |