Permit Number: T07CM03029
Parcel: 11520005D

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03029
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; Central District; 9,625 Square Feet of Warehouse; $7,605.77
12/10/2007 DAVID BELL LANDFILL REVIEW Approved
12/10/2007 MARTIN BROWN FIRE REVIEW Denied Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.

Also, reference is made to existing fire hydrants. Please include approved water plan from Tucson Water.

Clarify Fire Department Connection location for ware house.
12/11/2007 TERRY STEVENS ZONING REVIEW Denied 12/12/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
12/11/2007 ROBERT SHERRY WATER REVIEW Denied Provide a letter from Tucson Water confirming that the use of a 5/8" water meter (¾" water meters are not available from Tucson Water) will be allowed for this project (20 fixture units equates to a demand of 14 GPM)
12/19/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved DATE: December 19, 2007
SUBJECT: Warehouse
TO:
LOCATION: 1953 W Grant Road, T14S, R13E, Section 3, Ward 1
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07OT03029 (First Review)


RESUBMITTAL REQUIRED: Building Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed building plan for the above referenced property. Engineering Division has approvd the building plan. Please take note of the following review comments

Building Plan

1. Approval for building only. Must comply with zoning requirements - proposed building location must match approved development plan location. Zoning will verify.

2. Construction for building may not begin until development plan has been approved. In addition, if grading permit is required it will also need to be approved prior to start of construction.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
12/20/2007 GERRY KOZIOL WWM REVIEW Denied 1. SHC OFFICE- BUILDING #1
2. NEEDS WASTEWATER 8TH FL REVIEW & APPRV OF LOCATION/METHOD OF CONNECTION (EXISTING PRIVATE SEWER)

Final Status

Task End Date Reviewer's Name Type of Review Description
12/21/2007 CINDY AGUILAR APPROVAL SHELF Completed
12/21/2007 CINDY AGUILAR OUT TO CUSTOMER Completed